{"schema_version":"1.2","pwsid":"WI1140142","system_name":"WAUPUN CORRECTIONAL INST","city":"WAUPUN","state":"WI","population_served":3706,"source_type":"GW","summary":"WAUPUN CORRECTIONAL INST serves approximately 3,706 people in WAUPUN, Wisconsin. Based on contaminant analyses from DNR, WQP, EPA ECHO, EPA UCMR5, 2 contaminants have been measured above federal EPA standards (MCL) and 4 exceed health-based guidelines. The most significant finding is Combined Radium (226+228) at 6.3 pCi/L, which is 1.3x the EPA legal limit. Data is drawn from source-level compliance monitoring and covers 2014 through 2026. Results reflect conditions at the point of collection (wells, treatment plants), not necessarily at the tap.","data_period":{"start":"2014-07-09","end":"2026-04-06"},"contaminants_tested":105,"contaminants_detected":19,"exceedances":2,"guideline_exceedances":4,"contaminants":[{"name":"Chlorine (free)","code":"0700","cas_number":null,"group":"disinfectants","section":"other_detected","measured_value":0.99,"unit":"mg/L","sample_date":"2026-04-06","source":"DNR","source_scope":"source_monitoring","health_guideline_value":4,"health_guideline_source":"EPA MCLG","epa_mcl_value":4,"status":"below_limits","detection_limit":null},{"name":"Selenium","code":"1045","cas_number":null,"group":"inorganics","section":"other_detected","measured_value":0.0015,"unit":"mg/L","sample_date":"2026-02-02","source":"DNR","source_scope":"source_monitoring","health_guideline_value":0.05,"health_guideline_source":"EPA MCLG","epa_mcl_value":0.05,"status":"below_limits","detection_limit":null},{"name":"Fluoride (natural)","code":"FLUORIDE","cas_number":"16984-48-8","group":"inorganics","section":"other_detected","measured_value":0.18,"unit":"mg/L","sample_date":"2026-02-02","source":"DNR","source_scope":"source_monitoring","health_guideline_value":4,"health_guideline_source":"EPA MCLG","epa_mcl_value":4,"status":"below_limits","detection_limit":null},{"name":"Barium","code":"BARIUM","cas_number":"7440-39-3","group":"inorganics","section":"other_detected","measured_value":0.21,"unit":"mg/L","sample_date":"2026-02-02","source":"DNR","source_scope":"source_monitoring","health_guideline_value":1,"health_guideline_source":"OEHHA PHG 2003 (hypertension endpoint)","epa_mcl_value":2,"status":"below_limits","detection_limit":null},{"name":"Uranium","code":"4006","cas_number":"7440-61-1","group":"radionuclides","section":"other_detected","measured_value":0.211,"unit":"ug/L","sample_date":"2026-02-02","source":"DNR","source_scope":"source_monitoring","health_guideline_value":0.0005,"health_guideline_source":"OEHHA PHG","epa_mcl_value":0.03,"status":"below_limits","detection_limit":null},{"name":"Combined Radium (226+228)","code":"4010","cas_number":null,"group":"radionuclides","section":"legal_violation","measured_value":6.3,"unit":"pCi/L","sample_date":"2026-02-02","source":"DNR","source_scope":"source_monitoring","health_guideline_value":0,"health_guideline_source":"EPA MCLG","epa_mcl_value":5,"status":"exceeds_legal_limit","detection_limit":null},{"name":"Gross Alpha Radiation (excluding Radon and Uranium)","code":"4000_EXCL","cas_number":null,"group":"radionuclides","section":"legal_violation","measured_value":16.5,"unit":"pCi/L","sample_date":"2026-02-02","source":"DNR","source_scope":"source_monitoring","health_guideline_value":null,"health_guideline_source":null,"epa_mcl_value":15,"status":"exceeds_legal_limit","detection_limit":null},{"name":"Haloacetic Acids (HAA5)","code":"2456","cas_number":null,"group":"dbps","section":"other_detected","measured_value":6.2,"unit":"ug/L","sample_date":"2025-08-19","source":"DNR","source_scope":"source_monitoring","health_guideline_value":0.0001,"health_guideline_source":"EWG Health Guideline","epa_mcl_value":0.06,"status":"below_limits","detection_limit":null},{"name":"Total Trihalomethanes (TTHMs)","code":"2950","cas_number":null,"group":"dbps","section":"other_detected","measured_value":14.4,"unit":"ug/L","sample_date":"2025-08-19","source":"DNR","source_scope":"source_monitoring","health_guideline_value":0.00015,"health_guideline_source":"EWG Health Guideline","epa_mcl_value":0.08,"status":"below_limits","detection_limit":null},{"name":"cis-1,2-Dichloroethylene","code":"2943","cas_number":"156-59-2","group":"vocs","section":"other_detected","measured_value":0.21,"unit":"ug/L","sample_date":"2024-05-15","source":"DNR","source_scope":"source_monitoring","health_guideline_value":0.07,"health_guideline_source":"EPA MCLG","epa_mcl_value":0.07,"status":"below_limits","detection_limit":null},{"name":"trans-1,2-Dichloroethylene","code":"2944","cas_number":null,"group":"other","section":"other_detected","measured_value":0.32,"unit":"ug/L","sample_date":"2024-05-15","source":"DNR","source_scope":"source_monitoring","health_guideline_value":null,"health_guideline_source":null,"epa_mcl_value":null,"status":"detected","detection_limit":null},{"name":"Toluene","code":"2964","cas_number":null,"group":"other","section":"other_detected","measured_value":0.47,"unit":"ug/L","sample_date":"2024-11-04","source":"DNR","source_scope":"source_monitoring","health_guideline_value":null,"health_guideline_source":null,"epa_mcl_value":null,"status":"detected","detection_limit":null},{"name":"Total Xylenes","code":"2969","cas_number":"1330-20-7","group":"organic","section":"other_detected","measured_value":0.49,"unit":"ug/L","sample_date":"2024-11-04","source":"DNR","source_scope":"source_monitoring","health_guideline_value":0.5,"health_guideline_source":"WHO Guideline","epa_mcl_value":10,"status":"below_limits","detection_limit":null},{"name":"Nitrate (as N)","code":"NITRATE","cas_number":"14797-55-8","group":"inorganics","section":"other_detected","measured_value":0.13,"unit":"mg/L","sample_date":"2024-05-15","source":"DNR","source_scope":"source_monitoring","health_guideline_value":10,"health_guideline_source":"EPA MCLG","epa_mcl_value":10,"status":"below_limits","detection_limit":null},{"name":"Chlorine (total residual)","code":"0700_TOTAL","cas_number":null,"group":"disinfectants","section":"other_detected","measured_value":0.79,"unit":"mg/L","sample_date":"2024-10-03","source":"DNR","source_scope":"source_monitoring","health_guideline_value":4,"health_guideline_source":"EPA MCLG","epa_mcl_value":4,"status":"below_limits","detection_limit":null},{"name":"Chromium (total)","code":"CHROMIUM","cas_number":"7440-47-3","group":"inorganics","section":"other_detected","measured_value":190,"unit":"ug/L","sample_date":"2022-05-24","source":"WQP","source_scope":"regional_groundwater","health_guideline_value":0.1,"health_guideline_source":"EPA MCLG","epa_mcl_value":0.1,"status":"exceeds_legal_limit","detection_limit":null},{"name":"Nickel","code":"1036","cas_number":null,"group":"inorganics","section":"other_detected","measured_value":0.0012,"unit":"mg/L","sample_date":"2023-04-17","source":"DNR","source_scope":"source_monitoring","health_guideline_value":0.012,"health_guideline_source":"OEHHA PHG","epa_mcl_value":null,"status":"below_limits","detection_limit":null},{"name":"Arsenic","code":"ARSENIC","cas_number":"7440-38-2","group":"inorganics","section":"other_detected","measured_value":7.71,"unit":"ug/L","sample_date":"2022-06-01","source":"WQP","source_scope":"regional_groundwater","health_guideline_value":0.000004,"health_guideline_source":"OEHHA PHG","epa_mcl_value":0.01,"status":"exceeds_guideline","detection_limit":null},{"name":"Lead (90th Percentile)","code":"PB90","cas_number":"7439-92-1","group":"lead_copper","section":"guideline_exceedance","measured_value":0.00087,"unit":"mg/L","sample_date":"2025-06-30","source":"EPA ECHO","source_scope":"federal_program","health_guideline_value":0.0002,"health_guideline_source":"OEHHA PHG","epa_mcl_value":null,"status":"exceeds_guideline","detection_limit":null},{"name":"Copper (90th Percentile)","code":"COPPER","cas_number":"7440-50-8","group":"lead_copper","section":"guideline_exceedance","measured_value":930,"unit":"ug/L","sample_date":"2025-04-24","source":"DNR","source_scope":"source_monitoring","health_guideline_value":0.3,"health_guideline_source":"OEHHA PHG","epa_mcl_value":null,"status":"exceeds_guideline","detection_limit":null},{"name":"PFOS (Perfluorooctane Sulfonate)","code":"PFOS","cas_number":"1763-23-1","group":"pfas","section":"pfas","measured_value":0.66,"unit":"ng/L","sample_date":"2023-04-17","source":"DNR","source_scope":"source_monitoring","health_guideline_value":0,"health_guideline_source":"EPA MCLG","epa_mcl_value":0.004,"status":"below_limits","detection_limit":null}],"sources":[{"name":"DNR","url":"https://apps.dnr.wi.gov/dwsportalpub"},{"name":"WQP","url":"https://www.waterqualitydata.us/"},{"name":"EPA ECHO","url":"https://echo.epa.gov/"},{"name":"EPA UCMR5","url":"https://www.epa.gov/dwucmr/fifth-unregulated-contaminant-monitoring-rule"}],"pfas_combined_display":{"value":0.66,"unit":"ng/L","sample_date":"2023-04-17","note":"Legacy 2016 EPA Health Advisory combined PFOA+PFOS metric. Not a current MCL."},"well_counts":{"active":2,"retired":1,"facilities_synced_at":"2026-04-11T13:48:07.246Z"},"historical_wells":[],"has_only_historical_data":false,"pfas_hazard_index":null,"tthm_lraa":[{"monitoring_point":"system_wide","value":14.4,"unit":"ug/L","quarters_used":["2022Q3","2023Q3","2024Q3","2025Q3"],"sample_count":8,"mcl":80,"exceeds_mcl":false}],"haa5_lraa":[{"monitoring_point":"system_wide","value":6.2,"unit":"ug/L","quarters_used":["2022Q3","2023Q3","2024Q3","2025Q3"],"sample_count":8,"mcl":60,"exceeds_mcl":false}]}